Case: T09FR01109

Parcel: 124040760


Addresses:

1509 E 2ND ST

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
05/11/2009 VIOL - BUILDING SVCS & SYSTEMS Approved
03/31/2009 VIOL - BUILDING SVCS & SYSTEMS Violation 605.1 Abatement of electrical hazards. Identified electrical
hazards shall be abated. Identified hazardous electrical conditions
in permanent wiring shall be brought to the attention of
the code official responsible for enforcement of the ICC Electrical
Code. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used.

____Cover plates needed for all outlets:
____outlet under south-east stairs.
____outlet on north-side of courtyard near pool room.
03/31/2009 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.

____Remove extension cord from east building. It is currently affixed to the building and being used for a water pump.