Inspection History Details
Inspection Status: Cancelled
Inspection History: INSP - FULL
Case Number - T09FR01078
Inspection Description - INSP - FULL
Inspection Status - Cancelled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/22/2009 | INSP - FULL | Cancelled | THIS T O NUMBER WAS VOIDED. A NEW REPORT WILL BE GENERATED AND SENT TO THE CORRECT ADDRESS | |
03/25/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION FOR THE ABOVE ADDRESS THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. 1) THE CHECK VALVE ON THE RISER IS NOT SEATING PROPERLY AND IS LEAKING WATER INTO THE SUPPLY. GASKETS ON THE CLAPPER VALVE ARE CORRODED. THE CHECK VALVE SHALL BE REPAIRED OR REPLACED. |