Case: T09FR01041

Parcel: 13101053B


Addresses:

1255 S SWAN RD

Inspection Status: Approved

Inspection History: INSP - AST

Date Description Inspector Results Comments
08/25/2009 INSP - AST Approved Approved
03/23/2009 INSP - AST Correction Required 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires.

- Emergency venting must be installed. The vents must be the appropriate size for the tank. The tank manufacturer determines the size of vent required and the volume of venting required.