Inspection History Details
Inspection Status: Approved
Inspection History: INSP - AST
Case Number - T09FR01041
Inspection Description - INSP - AST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2009 | INSP - AST | Approved | Approved | |
| 03/23/2009 | INSP - AST | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. - Emergency venting must be installed. The vents must be the appropriate size for the tank. The tank manufacturer determines the size of vent required and the volume of venting required. |