Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR01007

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/18/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.

_____. Remove all storage from obstructing the electrical service equipment located in the back room.
03/18/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical
hazards shall be abated. Identified hazardous electrical conditions
in permanent wiring shall be brought to the attention of
the code official responsible for enforcement of the ICC Electrical
Code. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used.

_____1. Remove the breaker stops from the electrical panel located in the back room.