Case: T09FR00955

Parcel: 13101053B


Addresses:

1255 S SWAN RD

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
03/03/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.6 Unapproved conditions.
Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
*** Provide cover for junction boxes in N. Bldg:

_____ S/W corner _____ E. wall _____ ceiling x3
03/03/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.4 - Multiplug adapters.
Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
***Remove multiplug adaptors:

_____ N. Bldgm, N/W corner _____ N. Bldg, N. Wall, desk
Replace with approved multiplug adaptors:
TFC 605.4.1 - Power tap design.
Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363.

TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
03/03/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.1 - Abatement of electrical hazards.
Identified electrical hazards shall be abated.

_____ Repair electrical wiring/conduit N. Bldg, N/E corner

_____ Remove electrical wiring formerly serving dynometer