Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T09FR00955
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2009 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. *** Provide cover for junction boxes in N. Bldg: _____ S/W corner _____ E. wall _____ ceiling x3 |
|
| 03/03/2009 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ***Remove multiplug adaptors: _____ N. Bldgm, N/W corner _____ N. Bldg, N. Wall, desk Replace with approved multiplug adaptors: TFC 605.4.1 - Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. |
|
| 03/03/2009 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.1 - Abatement of electrical hazards. Identified electrical hazards shall be abated. _____ Repair electrical wiring/conduit N. Bldg, N/E corner _____ Remove electrical wiring formerly serving dynometer |