Case: T09FR00953

Parcel: 13408276A


Addresses:

8301 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
04/22/2009 INSP - FULL Approved all violations have been corrected.
03/26/2009 INSP - FULL Partial Approval All violations noted were brought into compliance. When Hood cleaned, the company found the hinges on the roof blower to be missing. Will have them fixed by next week. approval pending.
03/13/2009 INSP - FULL Violation On 3/12/09 you recieved a Full Fire Inspection by the Tucson Fire Department. The following Tucson Fire Code Violations were noted:

Problem: IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
Correction: You will remove from service, the powerstrip that you wired an extension cord to. This work has removed the UL listing from this appliance and it is deemed a hazardous condition. Replace it with a UL listed powerstrip that has not been altered.
03/13/2009 INSP - FULL Violation Problem: IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
Correction: You will provide a cover box for the open wiring splice that is on your kitchen ceiling ventilation system.
03/13/2009 INSP - FULL Violation Problem: IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
Correction: You stated that your hood system ductwork has never been cleaned from hood through to the roof. You will have your duct work cleaned in this manner by a qualified individual or company. Paperwork of this cleaning will be provided to the fire official upon reinspection on 3/26/09.
03/13/2009 INSP - FULL Violation 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices ffecting means of egress shall be subject to approval of the fire code official.
Correction: You will maintain your middle kitchen exit free of dough carts, furnishings, or other obstructions that impede the immediate exiting of employees in an emergency situation.


The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated.

Property Representative Signature: _________________________.

Fire Inspector Signature: _________________________(791-4502).

Reinspection Date: ___/___/___ or later.

___Approved

___Not Approved