Case: T09FR00947

Parcel: 13409018B


Addresses:

8578 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00947

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/22/2009 INSP - FULL Approved Lee Ray from devlopment services issued an administrative C of O. The exit that is soldered has been approved as eliminated from the existing structure by development services. It has the required number of exits per Building and Fire Code. All Fire code violations have been corrected.
03/13/2009 INSP - FULL Violation Problem: IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
Correction: You will place a faceplate on open wall outlet box behind your deep fat fryer.
03/13/2009 INSP - FULL Violation Problem: IFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment.
Correction: You will provide a clear access path to your electric panel.
03/13/2009 INSP - FULL Violation 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional
and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED.
Correction: You will contact Development Services for a building inspector to inspect your blocked East most exit in kitchen. Upon approval on the building official, a sign shall be affixed to the exterior portion of the door stating that it is blocked.