Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/30/2009 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. |
| 03/12/2009 |
INSP - FULL |
|
Scheduled |
1.) TFC 901.6 THE MINIMUM DISTANCE BETWEEN SPRINKLER HEADS IS 6 FEET. SPRINKLER HEADS IN UNIT #2 NURSES STATION AND IN ACTIVITY ROOM MUST BE RELOCATED TO MAINTAIN AT LEAST 6' SPACING. |
| 03/12/2009 |
INSP - FULL |
|
Scheduled |
2.) TFC 1008.1.8 THE REAR EGRESS DOOR FROM KITCHEN DRY STORAGE ROOM MUST HAVE THE DOUBLE KEYED DEAD BOLT REPLACED WITH A THUMB TURN DEAD BOLT. |