Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T09FR00936
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2009 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. | |
| 03/12/2009 | INSP - FULL | Scheduled | 1.) TFC 901.6 THE MINIMUM DISTANCE BETWEEN SPRINKLER HEADS IS 6 FEET. SPRINKLER HEADS IN UNIT #2 NURSES STATION AND IN ACTIVITY ROOM MUST BE RELOCATED TO MAINTAIN AT LEAST 6' SPACING. | |
| 03/12/2009 | INSP - FULL | Scheduled | 2.) TFC 1008.1.8 THE REAR EGRESS DOOR FROM KITCHEN DRY STORAGE ROOM MUST HAVE THE DOUBLE KEYED DEAD BOLT REPLACED WITH A THUMB TURN DEAD BOLT. |