Case: T09FR00935

Parcel: 12709005A


Addresses:

5550 E 5TH ST


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR00935

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
07/20/2009 VIOL - FIRE PROTECTION SYSTEMS Approved NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
03/12/2009 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.4 THE KITCHEN HOOD SYSTEM NEEDS TO BE EXTENDED TO PROVIDE DETECTOR AND VENTILATION OVER THE STOCK POT RANGE AND PROPER COVERAGE OF 6 BURNER GAS RANGE.

ANY EXTENSION OR MODIFICATION OF THE HOOD SYSTEM MUST BE DONE BY QUALIFIED PERSONNEL WITH AN APPROVED PERMIT.