Case: T09FR00918

Parcel: 11301146Z


Addresses:

1725 E PRINCE RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00918

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2009 INSP - FULL Approved APPROVED BY FIELD INSPECTION
04/16/2009 INSP - FULL Correction Required DEFICIENCIES FOUND DURING THE ANNUAL INSPECTION
1) STE. # 1749 - 4 PENDANT SPRINKLERS ARE TO FAR OFF WALLS

2) REPLACE FIRE DEPARTMENT CAPS

3) REPLACE MAIN DRAIN HANDLE
03/11/2009 INSP - FULL Correction Required FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED AND INSPECTED ANNUALLY.

1) THE MALE SWIVELS ARE MISSING FROM THE 3-WAY FIRE DEPARTMENT CONNECTION, IN 2 PLACES.

SPOKE WITH ROBIN @ 647-2727, SHE IS CONTACTING CUTLER F. P. FOR REPAIRS