Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2009 | INSP - FULL | Approved | APPROVED BY FIELD INSPECTION | |
04/16/2009 | INSP - FULL | Correction Required | DEFICIENCIES FOUND DURING THE ANNUAL INSPECTION 1) STE. # 1749 - 4 PENDANT SPRINKLERS ARE TO FAR OFF WALLS 2) REPLACE FIRE DEPARTMENT CAPS 3) REPLACE MAIN DRAIN HANDLE |
|
03/11/2009 | INSP - FULL | Correction Required | FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE TESTED AND INSPECTED ANNUALLY. 1) THE MALE SWIVELS ARE MISSING FROM THE 3-WAY FIRE DEPARTMENT CONNECTION, IN 2 PLACES. SPOKE WITH ROBIN @ 647-2727, SHE IS CONTACTING CUTLER F. P. FOR REPAIRS |