Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: INSP - SELF INSPECTION PROGRAM
| Date |
Description |
Inspector |
Results |
Comments |
| 03/23/2009 |
INSP - SELF INSPECTION PROGRAM |
|
Approved |
|
| 03/10/2009 |
INSP - SELF INSPECTION PROGRAM |
|
Correction Required |
1. 1IFC 901.6: If you have a sprinkler system in your building, has it been tested and serviced within the past 12 months? Alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. |
| 03/10/2009 |
INSP - SELF INSPECTION PROGRAM |
|
Correction Required |
2. IFC 315.2.1: Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. |