Case: T09FR00857

Parcel: 11451137B

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/30/2009 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
03/10/2009 INSP - FULL Violation 1.) TFC 605.6 THE ELECTRICAL JUNCTION BOX ON FIRE RISER TAMPER SWITCH NEEDS A COVER PLATE INSTALLED.
03/10/2009 INSP - FULL Violation 2.) TFC 510.1 SPRINKLER SYSTEM RISER ROOM DOOR NEEDS A SIGN STATING "RISER ROOOM" AFIXED ON THE EXTERIOR SIDE OF THE DOOR.
03/10/2009 INSP - FULL Violation 3.) TFC 901.6 SEAL GAPS ABOVE THE SPRINKLER HEAD ESCUTCHOENS THROUGHOUT THE FACILITY.
03/10/2009 INSP - FULL Violation 4.) TFC 1008.1.8 REAR EXIT DOOR FROM KITCHEN MUST HAVE THE DOUBLE DEAD BOLT REMOVED AND REPLACED WITH A DEAD BOLT WITH A THUMB TURN LATCH.
03/10/2009 INSP - FULL Violation 5.) TFC 1008.1.8.5 REAR EXIT DOOR FROM KITCHEN MUST HAVE THE SLIDE BOLT LATCH REMOVED.
03/10/2009 INSP - FULL Violation 6.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN FRONT, BIG ROOM CLOSET.
03/10/2009 INSP - FULL Violation 7.) TFC 906.1 IN FRONT, BIG ROOM CLOSET REPLACE CEILING TILE AROUND SPRINKLER HEAD. TILE IS BOWED DOWN IN THE MIDDLE CAUSING THE ESCUTCHEON TO BLOCK SPRAY PATTERN OF WATER.
03/10/2009 INSP - FULL Approved NOTE: FIRE ALARM AND SPRINKLER SYSTEM ANNUAL REPORTS WERE SUBMITTED AT TIME OF INSPECTION.

FIRE DRILL RECORDS ARE IN COMPLIANCE.