Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2009 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. | |
| 03/10/2009 | INSP - FULL | Violation | 1.) TFC 605.6 THE ELECTRICAL JUNCTION BOX ON FIRE RISER TAMPER SWITCH NEEDS A COVER PLATE INSTALLED. | |
| 03/10/2009 | INSP - FULL | Violation | 2.) TFC 510.1 SPRINKLER SYSTEM RISER ROOM DOOR NEEDS A SIGN STATING "RISER ROOOM" AFIXED ON THE EXTERIOR SIDE OF THE DOOR. | |
| 03/10/2009 | INSP - FULL | Violation | 3.) TFC 901.6 SEAL GAPS ABOVE THE SPRINKLER HEAD ESCUTCHOENS THROUGHOUT THE FACILITY. | |
| 03/10/2009 | INSP - FULL | Violation | 4.) TFC 1008.1.8 REAR EXIT DOOR FROM KITCHEN MUST HAVE THE DOUBLE DEAD BOLT REMOVED AND REPLACED WITH A DEAD BOLT WITH A THUMB TURN LATCH. | |
| 03/10/2009 | INSP - FULL | Violation | 5.) TFC 1008.1.8.5 REAR EXIT DOOR FROM KITCHEN MUST HAVE THE SLIDE BOLT LATCH REMOVED. | |
| 03/10/2009 | INSP - FULL | Violation | 6.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN FRONT, BIG ROOM CLOSET. | |
| 03/10/2009 | INSP - FULL | Violation | 7.) TFC 906.1 IN FRONT, BIG ROOM CLOSET REPLACE CEILING TILE AROUND SPRINKLER HEAD. TILE IS BOWED DOWN IN THE MIDDLE CAUSING THE ESCUTCHEON TO BLOCK SPRAY PATTERN OF WATER. | |
| 03/10/2009 | INSP - FULL | Approved | NOTE: FIRE ALARM AND SPRINKLER SYSTEM ANNUAL REPORTS WERE SUBMITTED AT TIME OF INSPECTION. FIRE DRILL RECORDS ARE IN COMPLIANCE. |