Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T09FR00826

Parcel: 13331159T


Addresses:

8800 E BROADWAY BL


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T09FR00826

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
03/06/2009 INSP - FULL Violation Problem: IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
Correction: You will have the extinguisher that is on the floor of your manager's office placed on a bracket on a wall.
03/06/2009 INSP - FULL Violation Problem: IFC 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.
Correction: You will provide the fire marshall with copies of your last two system inspections and maintain a record on premises of future inspections ( to be viewed by the fire marshal on subsequent inspections).
03/06/2009 INSP - FULL Violation 505.1 Address numbers. (cot mod) New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements.
Correction: You will install numbers on your building in accordance with Pima County Adreesing Code ( attached to report).
03/05/2009 INSP - FULL Violation Problem: IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
Correction: You will have your cord on your smart wash system replaced by a certified electrician and provide documentation of such.
03/05/2009 INSP - FULL Violation 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official.
Correction: You will maintain your exits free of carts, racks, etc at ALL times. The key locking mechanism on your SE exit from the kitchen will be replaced with a thumb-bolt turn lock. The security lock at the top of the door that initiates an audible alarm is fine as long as it does not prevent exiting from the door.