Case: T09FR00825

Parcel: 11012005A


Addresses:

2585 N WYATT DR


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00825

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/20/2009 INSP - FULL Approved
03/05/2009 INSP - FULL Correction Required DURING THE LAST SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. HAVE THE CONTRACTOR OF RECORD FORWARD A COPY OF HIS CORRECTION REPORT.

1) THE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL INSPECTION

2) THE GUAGES SHALL BE REPLACED OR RECALIBRATED