Case: T09FR00780

Parcel: 12404032C


Addresses:

1423 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - FIRE SERVICE FEATURES

Date Description Inspector Results Comments
03/13/2009 VIOL - FIRE SERVICE FEATURES Approved
02/27/2009 VIOL - FIRE SERVICE FEATURES Violation 510.1 Identification. Fire protection equipment shall be identified
in an approved manner. Rooms containing controls for
air-conditioning systems, sprinkler risers and valves, or other
fire detection, suppression or control elements shall be identified
for the use of the fire department. Approved signs required
to identify fire protection equipment and equipment location,
shall be constructed of durable materials, permanently
installed and readily visible.

____Label riser room door "RISER ROOM"
02/27/2009 VIOL - FIRE SERVICE FEATURES Violation 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash,
storage and other materials or objects shall not be placed or
kept near fire hydrants, fire department inlet connections or
fire protection system control valves in a manner thatwould
prevent such equipment or fire hydrants from being immediately
discernible. The fire department shall not be deterred
or hindered from gaining immediate access to fire protection
equipment or fire hydrants.

____Trim vegetation around Fire Dept. Connections.