Case: T09FR00761

Parcel: 13411361C


Addresses:

1114 S SARNOFF DR

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/12/2009 INSP - FULL Approved All violations have been corrected.
02/25/2009 INSP - FULL Violation #1 Problem: IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
Correction: Remove multiplug extension cords behind front merchandise counter and ( in kitchen from hole in ceiling tile- removed on inspection).
02/25/2009 INSP - FULL Violation # 2 Problem: IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction shall be maintained.
Correction: Replace ceiling tiles where missing in stock room and in kitchen where vent is open to glue lam beam and attack space.
02/25/2009 INSP - FULL Violation # 3 Problem: IFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
Remove the slide bolt lock from the NW kitchen exit.
02/25/2009 INSP - FULL Violation # 4 Problem: IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity.
Correction: You will secure your small CO2 cylinder in kitchen.
02/25/2009 INSP - FULL Violation # 5 Problem: IFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
Correction: You will cause your emergency lighting to operate properly.
02/25/2009 INSP - FULL Violation # 6 Problem: IFC 1008.2 Gates. Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors.
Problem: IFC IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,Mand S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
Correction: You will post a sign about your security gates on your East Exits that states: These doors to remain unlocked while the building is occupied. It shall be conspicuous and durable in large enough lettering to be read and in contrast to its background. These signs are already over your exit doors and must be maintained at each door or gate in the path of the main egress.
02/25/2009 INSP - FULL Violation # 7 Problem: IFC 1011.5.3 Power source. Exit signs shall be illuminated at all times.
Correction: You will cause your exit signs to light.
02/25/2009 INSP - FULL Violation # 8 Problem: IFC 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.
Correction: Remove Christmas garland/wreaths stored within 1 inch of the ceiling lighting. Heat can cause ignition. Light produces heat.
02/25/2009 INSP - FULL Violation # 9 Problem: IFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
Correction: Remove ladders stored at top of rack storage in stock room. They are stored within inches of the ceiling where there are missing ceiling tiles. This is a good avenue and fuel for firespread into your attic space in the event of a fire.