Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2009 | VIOL - MEANS OF EGRESS | Approved | ||
| 03/17/2009 | VIOL - MEANS OF EGRESS | Partial Approval | 1008.1.8.3 Complete | |
| 03/17/2009 | VIOL - MEANS OF EGRESS | Continued | Exit sign work order in place | |
| 02/24/2009 | VIOL - MEANS OF EGRESS | Correction Required | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. " Please replace the damaged sign. |
|
| 02/24/2009 | VIOL - MEANS OF EGRESS | Correction Required | 1011.4 Internally illuminated exit signs. Internally illuminated exit signs shall be listed and labeled and shall be installed in accordance with the manufacturer's instructions and Section 2702 of the International Building Code. Exit signs shall be illuminated at all times. " The exit sign in the rear storage is not working. Please repair or replace the sign to ensure it is lit at all times and has a minimum of a 90 minute back up power source. |