Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T09FR00737

Parcel: 13634796B


Addresses:

3797 S KOLB RD

Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Date Description Inspector Results Comments
05/04/2009 VIOL - MOTOR FUEL DISPENSING Approved
03/17/2009 VIOL - MOTOR FUEL DISPENSING Continued New test being performed. Results should be in about 3 weeks.
02/24/2009 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.2 Emergency shutoff valves. Automatic emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.

" Please provide test results
02/24/2009 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

" Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.

" Remove the plugs that are in the secondary piping leak detection tubes.