Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2009 | VIOL - BUILDING SVCS & SYSTEMS | Approved | Repairs made, panel cleared | |
| 02/24/2009 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. " Do not store combustible materials within the specified area |
|
| 02/24/2009 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. " Replace the cover on the junction box |