Case: T09FR00737

Parcel: 13634796B


Addresses:

3797 S KOLB RD

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
03/17/2009 VIOL - BUILDING SVCS & SYSTEMS Approved Repairs made, panel cleared
02/24/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

" Do not store combustible materials within the specified area
02/24/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes.

" Replace the cover on the junction box