Case: T09FR00736

Parcel: 136244580


Addresses:

2750 S KOLB RD


Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T09FR00736

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2009 VIOL - MOTOR FUEL DISPENSING Approved
02/24/2009 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.2 Emergency shutoff valves. Automatic emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.

" Please provide test results.
02/24/2009 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

" Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.