Inspection Status: Approved
Inspection History: VIOL - MOTOR FUEL DISPENSING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2009 | VIOL - MOTOR FUEL DISPENSING | Approved | ||
| 02/24/2009 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2.2 Emergency shutoff valves. Automatic emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage. " Please provide test results. |
|
| 02/24/2009 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation. " Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer. |