Case: T09FR00736

Parcel: 136244580


Addresses:

2750 S KOLB RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR00736

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
03/17/2009 VIOL - BUILDING SVCS & SYSTEMS Approved Panel blanks replaced and panel clear
02/24/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

" Replace the "blanks" on circuit breaker box "G" and do not store combustible materials within the specified area.