Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T09FR00708
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/19/2009 | VIOL - FIRE PROTECTION SYSTEMS | Approved | NOTED DEFICIENCIES WERE REPAIRED AND APPROVED. PORTABLE FIRE EXTINGUISHER WAS REPLACED. | |
02/19/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 1. TFC 901.6 THE KITCHEN HOOD SYSTEM MUST BE MAINTAINED AND IN PROPER OPERATING ORDER. DURING SEMI-ANNUAL INSPECTION THE AUTOMATIC DETECTION SYSTEM DID NOT WORK DUE TO BUILD UP OF GREASE IN CONDUIT. REPLACE CONDUIT AS NECESSARY BY A QUALIFIED TECHNICIAN. | |
02/19/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 2.) TFC 906.2 PORTABLE FIRE EXTINGUISHER WITH RUST ON BOTTOM MUST BE REPLACED. | |
02/19/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | THESE ITEMS MUST BE REPAIRED IN 30 DAYS. FAX COPY OF REPAIRS TO FAX NUMBER SHOWN ON BOTTOM OF REPORT. |