Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR00708

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2009 VIOL - FIRE PROTECTION SYSTEMS Approved NOTED DEFICIENCIES WERE REPAIRED AND APPROVED. PORTABLE FIRE EXTINGUISHER WAS REPLACED.
02/19/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 1. TFC 901.6 THE KITCHEN HOOD SYSTEM MUST BE MAINTAINED AND IN PROPER OPERATING ORDER. DURING SEMI-ANNUAL INSPECTION THE AUTOMATIC DETECTION SYSTEM DID NOT WORK DUE TO BUILD UP OF GREASE IN CONDUIT. REPLACE CONDUIT AS NECESSARY BY A QUALIFIED TECHNICIAN.
02/19/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 2.) TFC 906.2 PORTABLE FIRE EXTINGUISHER WITH RUST ON BOTTOM MUST BE REPLACED.
02/19/2009 VIOL - FIRE PROTECTION SYSTEMS Correction Required THESE ITEMS MUST BE REPAIRED IN 30 DAYS. FAX COPY OF REPAIRS TO FAX NUMBER SHOWN ON BOTTOM OF REPORT.