Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2009 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Approved |
NOTED DEFICIENCIES WERE REPAIRED AND APPROVED. PORTABLE FIRE EXTINGUISHER WAS REPLACED. |
| 02/19/2009 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
1. TFC 901.6 THE KITCHEN HOOD SYSTEM MUST BE MAINTAINED AND IN PROPER OPERATING ORDER. DURING SEMI-ANNUAL INSPECTION THE AUTOMATIC DETECTION SYSTEM DID NOT WORK DUE TO BUILD UP OF GREASE IN CONDUIT. REPLACE CONDUIT AS NECESSARY BY A QUALIFIED TECHNICIAN. |
| 02/19/2009 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Violation |
2.) TFC 906.2 PORTABLE FIRE EXTINGUISHER WITH RUST ON BOTTOM MUST BE REPLACED. |
| 02/19/2009 |
VIOL - FIRE PROTECTION SYSTEMS |
|
Correction Required |
THESE ITEMS MUST BE REPAIRED IN 30 DAYS. FAX COPY OF REPAIRS TO FAX NUMBER SHOWN ON BOTTOM OF REPORT. |