Case: T09FR00683

Parcel: 135074550

Inspection Status: Approved

Inspection History: INSP - SELF INSPECTION PROGRAM

Case Number - T09FR00683

Inspection Description - INSP - SELF INSPECTION PROGRAM

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2009 INSP - SELF INSPECTION PROGRAM Approved Referred by J. Davis. I inspected and found that the storage is simple boxed items on a shelf up against the wall. It is not blocking hose streams or sprinklers.
02/19/2009 INSP - SELF INSPECTION PROGRAM Correction Required IFC 315.2.1: Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.