Inspection Status: Approved
Inspection History: INSP - SELF INSPECTION PROGRAM
| Date |
Description |
Inspector |
Results |
Comments |
| 03/06/2009 |
INSP - SELF INSPECTION PROGRAM |
|
Approved |
Referred by J. Davis. I inspected and found that the storage is simple boxed items on a shelf up against the wall. It is not blocking hose streams or sprinklers. |
| 02/19/2009 |
INSP - SELF INSPECTION PROGRAM |
|
Correction Required |
IFC 315.2.1: Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. |