Case: T09FR00672

Parcel: 13103224R


Addresses:

5180 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00672

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2009 INSP - FULL Approved Both discrepancies corrected.
02/18/2009 INSP - FULL Correction Required 01. An extension cord is used as permanent wiring in the boiler / mechanical room. Replace the extesion cord with permanent wiring.
INTERNATIONAL FIRE CODE (IFC) 605.5 Extension cords.
Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
02. The boiler / mechanical room is used to store combustibles and gas powered equipment. Remove all stored items from this room. IFC
315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms.
NOTE: The fire extinguishers are due their annual inspection / servicing. Please provide scheduled date for inspection.
SUSPENSE: 3/19/2009.