Case: T09FR00629

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR00629

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/18/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system.

_____1. Test all emergency lighting units and EXIT signs for emergency back-up power illunmination and repair any deficiencies.
NOTE: Provide documentation of the testing.
02/18/2009 VIOL - MEANS OF EGRESS Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges
shall be continuously maintained free from obstructions
or impediments to full instant use in the case of fire or
other emergency when the areas served by such exits are occupied.

_____1. Remove the storage from obstructing the the North exit door.
02/18/2009 VIOL - MEANS OF EGRESS Correction Required TFC Section 1028.8 Panic hardware. Where panic and fire exit hardware is installed,
the panic or fire exit hardware shall be the only locking device on the door except
where otherwise permitted in this code.

_____1. Remove the thumb-turn deadbolt from the exit door located in the back room.