Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T09FR00629

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR00629

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/18/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.

_____1. Remove the storage from obstructing the electrical service equipment located in the back room.



________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)


Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____

______________________
John E. Bieg