Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - LIQUID PETROLEUM GASES
Case Number - T09FR00612
Inspection Description - VIOL - LIQUID PETROLEUM GASES
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/17/2009 | VIOL - LIQUID PETROLEUM GASES | Violation | 3807.3 Clearance to combustibles.Weeds, grass, brush, trash and other combustible materials shall be kept a minimum of 10 feet (3048 mm) from LP-gas tanks or containers. 3807.4 Protecting containers from vehicles. Where exposed to vehicular damage due to proximity to alleys, driveways or parking areas, LP-gas containers, regulators and piping shall be protected in accordance with Section 312. 1) LPG containers in the alley are currently surrounded by combustible material and are exposed to vehicular damage. These need to be stored in an approved manner. |
|
02/17/2009 | VIOL - LIQUID PETROLEUM GASES | Violation | 3809.1 General. Storage of portable containers of 1,000 pounds (454 kg) or less, whether filled, partially filled or empty, at consumer sites or distributing points, and for resale by dealers or resellers shall comply with Sections 3809.2 through 3809.15. 1) Portable LPG containers cannot be stored inside the the building or tent. They must be stored outside and 10 ft. from any exit. |