Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T09FR00612
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/17/2009 | VIOL - MEANS OF EGRESS | Violation | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: 1. Group A having 50 or more occupants. 1) If your CofO has an occupant load of 50 or more then you will be required to install emergency lighting units that illuminate the means of egress during power supply failure. |
|
02/17/2009 | VIOL - MEANS OF EGRESS | Violation | 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. 1) Repair EXIT signs. |
|
02/17/2009 | VIOL - MEANS OF EGRESS | Violation | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,Mand S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. 1) Only the front/main door can have a double keyed lock. The others must have a thumbturn lock only. 2) Post a sign above the main door stating THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. |