Case: T09FR00612

Parcel: 117040500


Addresses:

628 N 4TH AV


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR00612

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
02/17/2009 VIOL - MEANS OF EGRESS Violation 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system for the following occupancies where such
occupancies require two or more means of egress:
1. Group A having 50 or more occupants.

1) If your CofO has an occupant load of 50 or more then you will
be required to install emergency lighting units that illuminate the
means of egress during power supply failure.
02/17/2009 VIOL - MEANS OF EGRESS Violation 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated.

1) Repair EXIT signs.
02/17/2009 VIOL - MEANS OF EGRESS Violation 1008.1.8.3 Locks and latches. Locks and latches shall
be permitted to prevent operation of doors where any of
the following exists:
2. In buildings in occupancy Group A having an
occupant load of 300 or less, Groups B, F,Mand S,
and in places of religious worship, the main exterior
door or doors are permitted to be equipped
with key-operated locking devices from the egress
side provided:
2.1. The locking device is readily distinguishable
as locked,
2.2. A readily visible durable sign is posted on
the egress side on or adjacent to the door
stating: THIS DOOR TO REMAIN
UNLOCKED WHEN BUILDING IS
OCCUPIED. The sign shall be in letters 1
inch (25 mm) high on a contrasting background,
2.3. The use of the key-operated locking device
is revokable by the fire code official for
due cause.

1) Only the front/main door can have a double keyed lock. The others must have a thumbturn lock only.
2) Post a sign above the main door stating THIS DOOR TO REMAIN
UNLOCKED WHEN BUILDING IS OCCUPIED.