Case: T09FR00584

Parcel: 10512055A


Addresses:

115 W LIMBERLOST DR


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00584

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/20/2009 INSP - FULL Approved REPAIR NOTICE TO SYSTEMS
04/10/2009 INSP - FULL Correction Required THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 2-12-09, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 115 W. LIMBERLOST. IF CORRECTED HAVE THE CONTRACTOR OF RECORF FORWARD THEIR REPORT.
02/12/2009 INSP - FULL Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR CONTRACTORS MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE.

1) THE WATER FLOW ALARMS (BELLS) ARE INCORRECTLY WIRED AND SHALL BE REPAIRED. WHEN REPAIRED A FLOW TEST SHALL BE PERFORMED TO DETERMINE THE ACCEPTABILITY OF REPAIRS.