Inspection Status: Correction Required
Inspection History: VIOL - FIRE SERVICE FEATURES
Case Number - T09FR00527
Inspection Description - VIOL - FIRE SERVICE FEATURES
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2009 | VIOL - FIRE SERVICE FEATURES | Correction Required | ____Fire hydrant missing. (South parking lot, center of complex.) 508.5.2 Inspection, testing and maintenance. Fire hydrant systems shall be subject to periodic tests as required by the fire code official. Fire hydrant systems shall be maintained in an operative condition at all times and shall be repaired where defective. Additions, repairs, alterations and servicing shall comply with approved standards. ***Replace hydrant immediately. |
|
02/05/2009 | VIOL - FIRE SERVICE FEATURES | Correction Required | ____NW gates welded shut, NE gates locked, blocks apparatus access. 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. *** Undo welds on following gates to provide access for apparatus immediately. Install T.F.D. approved key box and/or padlocks on both NW and NE gates. |