Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T09FR00513

Parcel: 13505149M

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/24/2009 INSP - FULL Approved All violations have been corrected. An appeal was sent to the Fire Marshall ( and granted) for no locks on the freezers and no sprinklers inside the freezers. The non permitted addition of a caged exit enclosure was referred over to DNR/ Community Services for investigation of need for permit.
02/05/2009 INSP - FULL Violation 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system and NFPA 13. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations
to fire protection systems shall be done in accordance with applicable standards.
Correction: You will extend your automatic fire sprinkler system to add coverage to your caged exit enclosure on the North side of your building. You will extend your sprinkler coverage to include both freezers that are on the North side of your building in the the fenced in area.
02/04/2009 INSP - FULL Violation Problem: IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity.
Correction: You will secure your CO2 tanks in the kitchen pantry, and the empty bottles outside in the caged area.
02/04/2009 INSP - FULL Violation Problem: IFC 906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view.
Corrrection: You will mount the extinguisher that is under the cash register in a more conspicuous place.
02/04/2009 INSP - FULL Violation Problem: IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction shall be maintained.
Correction: You will repair the holes ( replace missing or damaged tiles) in your ceiling tile over the projector. You will place a vent over open ductwork in the kitchen soda closet.
02/04/2009 INSP - FULL Violation Problem: IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
Correction: You will remove extension cord that is behind the drop down screen next to kitchen, and in downstairs hall way on the ceiling and into the mens room.
02/04/2009 INSP - FULL Violation 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official.
Correction: You will remove the surface key bolt locks that were installed on the exterior of your exit doors from your two freezer buildings.
02/04/2009 INSP - FULL Violation Problem: IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
Correction: You will place a cover on the open junction box that contains a wiring splice. ( over the back side of the exit sign in the South hall and near the womens restroom)
02/04/2009 INSP - FULL Violation 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed.
Correction: You will remove the sign that says THIS DOOR BLOCKED on interior of your West exit door from the main lounge. This is a required exit and can confuse people in an emergency.
02/04/2009 INSP - FULL Violation Problem: IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's
installation instructions.
Correction: You will have your fire extinguisher ( under the bar, in kitchen and all others not mounted) mounted on a bracket on the wall.
02/04/2009 INSP - FULL Violation 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use
of the fire department.
Correction: You will place a sign on the door which houses your sprinkler control valve ( upstairs in dressing room ).
02/04/2009 INSP - FULL Violation Problem: IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code
shall be prohibited.
Correction: You will remove orange adapter attached to plug on E wall of the business office.