Case: T09FR00489

Parcel: 103090370


Addresses:

3830 N HIGHWAY DR

Inspection Status: Approved

Inspection History: INSP - AST

Date Description Inspector Results Comments
02/10/2009 INSP - AST Approved Vents are inastalled and permit issued
02/05/2009 INSP - AST Correction Required FIRE INSPECTION REPORT


February 5, 2009


Empire Cat
3830 North Highway Dr.
Tucson, AZ 85705
T09FR00489


Mr. Jones,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on February 4th 2009. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. The 2006 International Fire Code with modifications requires compliance. A Re-inspection will be performed on or about February 18th, 2009.


3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent.

- Normally closed vent shall be installed on the oil tanks or the vent must discharge outside the building. This is also known as a pressure/vacuum style vent.


3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires.

- Emergency venting must be installed. The vents must be the appropriate size for the tank. The tank manufacturer determines the size of vent required and the volume of venting required.


The Oil filter draining tank must be emptied on a regular basis. (daily)