Case: T09FR00484

Parcel: 12512079B


Addresses:

3250 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
02/17/2009 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
02/03/2009 INSP - FULL Violation 1.) TFC 904.11.6.3 GREASE REMOVAL DEVICES AND DUCTS SHALL BE CLEANED AT INTERVALS NECESSARY TO PREVENT ACCUMULATION OF GREASE. CLEAN GREASE FROM KITCHEN HOOD SYSTEM ALL THE WAY UP TO THE ROOF.
02/03/2009 INSP - FULL Violation 2.) TFC 904.11.7 A SHEET METAL SEPARATION BAFFLE MUST BE INSTALLED, AT A MINIMUM OF 8" HIGH, BETWEEN GREASE FRYER AND GAS GRILL.
02/03/2009 INSP - FULL Violation 3.) TFC 904.11.6.1 GREASE REMOVAL BAFFLES SHALL BE IN PLACE WHEN COOKING EQUIPMENT IS BEING USED.
02/03/2009 INSP - FULL Violation 4.) TFC 1008.1.8.4 THE SLIDE BOLT LATCH ON REAR EXIT DOOR FROM KITCHEN MUST BE TREMOVED AND A THUMB TURN DEAD BOLT INSTALLED.