Case: T09FR00417

Parcel: 117120870


Addresses:

2 E CONGRESS ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00417

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2010 INSP - FULL Approved
03/19/2009 INSP - FULL Violation On 1-29-09, a fire prevention inspection was conducted at 2 East Congress, Tucson Arizona.

On 2-27-09, a re-inspection was conducted and the following International Fire Code 2003 Violation(s) was noted:

901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 901.6.1.

3 separate reports are required, and they are (IFC 901.6.1)

;
A). Fire sprinkler test and inspection report
B). Fire alarm test report
C). Fire pump test report

This letter is to inform you that abatement of these Tucson Fire Code violations must be completed by 4-2-09.
A re-inspection shall be conducted at that time to ensure compliance.

Failure to comply with these Tucson Fire Code requirements could result in civil litigation under; City of Tucson Ordinance 9609.

If you have questions or if I may be of any assistance please call me at 791-4502 extension 127.
01/30/2009 INSP - FULL Violation 1). Fire drill shall be conducted. Date shall be determined by 2-17-09.
IFC 405.2
2). 3 reports are need and they are (IFC 701.3):
A). Fire sprinkler test and inspection report
B). Fire alarm test report
C). Fire pump test report
3). Extend sprinkler to small shed in roof.
4). Repair emergency lights on 4th and 3rd floor lobbies