Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2009 | INSP - FULL | Violation | Problem: IFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Correction: Remove any objects blocking access to your electrical panel. ( done immediatly on site). |
|
| 02/03/2009 | INSP - FULL | Approved | ||
| 01/28/2009 | INSP - FULL | Violation | Problem: IFC 1011.4 Internally illuminated exit signs. Exit signs shall be illuminated at all times. Correction: Replace the bulb on your L side emergency exit sign /emergency lighting. |