Case: T09FR00400

Parcel: 13355231A

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00400

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/12/2009 INSP - FULL Approved
02/03/2009 INSP - FULL Violation Problem: IFC 1028.2 Reliability. Required exits shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied.
Correction: ( corrected immediatly per the inspector) You will remove all boxes, chairs, and other items that are blocking the full use of your NE exit.
02/03/2009 INSP - FULL Violation Problem: IFC 315.2.1 Ceiling clearance. Storage shall be maintained a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
Correction: Resituate all storage in stock area that comprimises the 18 inch clearance requirement in sprinklered buildings. Maintain that 18 inch clearance at all times.
02/03/2009 INSP - FULL Violation Problem: IFC 1014.4 Aisles. The required width of aisles shall be unobstructed.
Correction: Your Northmost Exit aisle is blocked with boxes of stock and items. The full width of that aisle must be maintained from W to E along its length. Remove items blocking aisle width.
02/03/2009 INSP - FULL Violation Problem: IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily opened from the egress side without the use of a key or special knowledge or effort.
Correction:Remove or replace the lock on your electrical room door so that it can be opened from the egress side.