Case: T09FR00396

Parcel: 136406740


Addresses:

9620 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/02/2009 INSP - FULL Approved Systems final test today and in FULL COMPIANCE. CLOSED!
02/02/2009 INSP - FULL Correction Required The Fire Alarm panel is now powered and back in service. The sprinkler company will be contacted for them to finalize the annual test.
01/29/2009 INSP - FULL Correction Required The Fire Alarm Panel has no power to the panel. Fire alarm system company contacted.
01/28/2009 INSP - FULL Correction Required The FIRE SRPINKLER System is overdue its annual servicing/inspection. A REPORT of OCCUPANCY INSPECTION issued with a 2/26/2009 suspense.
The Fire Alarm panel is showing no power. Manager Ashley notified to have repairs effected immediately.
01/28/2009 INSP - FULL Correction Required Sprinkler system serviced 1/28/09: all tested components operational. However; the interfacing of the fire sprinkler and fire alarm panel could not be tested because the alarm panel is not powered.