Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MOTOR FUEL DISPENSING
Case Number - T09FR00358
Inspection Description - VIOL - MOTOR FUEL DISPENSING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2009 | VIOL - MOTOR FUEL DISPENSING | Approved | Number 9 hose replaced | |
| 01/26/2009 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times. " Replace the cracked short hose on #9 and monitor hoses on #15 and 16. |
|
| 01/26/2009 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2.2 Emergency shutoff valves. Automatic emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage. " Please provide documentation of the test. |
|
| 01/26/2009 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation. " Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer. |