Case: T09FR00358

Parcel: 11601002A

Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T09FR00358

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Approved

Date Description Inspector Results Comments
02/10/2009 VIOL - MOTOR FUEL DISPENSING Approved Number 9 hose replaced
01/26/2009 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times.

" Replace the cracked short hose on #9 and monitor hoses on #15 and 16.
01/26/2009 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.2 Emergency shutoff valves. Automatic emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.

" Please provide documentation of the test.
01/26/2009 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

" Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.