Case: T09FR00311

Parcel: 134113640


Addresses:

8099 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00311

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2009 INSP - FULL Approved All violations have been corrected.
01/22/2009 INSP - FULL Violation Problem: IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
Correction: You will replace the missing escussion plate for the sprinkler head in your computer room.
01/22/2009 INSP - FULL Violation Problem: IFC 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate.
Correction: You will repair the door handle in your owners office as it is hardware on an exit door.
01/22/2009 INSP - FULL Violation Problem: IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
Correction: You will replace the missing blank in your breaker box that is located in the breakroom.
01/22/2009 INSP - FULL Violation Problem: IFC IFC 1011.1 Where required. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants.
Correction: You will place an exit sign over the opening leading to your rear exit so that all people in all areas of the production area can see where the exit path is.
01/22/2009 INSP - FULL Prior to Final Inspectn You will prepair a copy of your sprinkler system inspection/maintance for our records and keep a copy on site with you.