Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T09FR00260

Parcel: 12106001B


Addresses:

5851 E SPEEDWAY BL


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T09FR00260

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/20/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE

1) THE SPARE HEAD SPRINKLER BOX REQUIRES A WRENCH FOR THE STAR MODEL E SPRINKLERS

2) THE INSPECTORS TEST VALVE AND THE MAIN CONTROL VALVE REQUIRE IDENTIFICATION SIGNS

3) WEST WAREHOUSE, NORTHWEST ROOM, A BRANCH LINE NEEDS A HANGER.

4) WEST WAREHOUSE, EAST WALL, THE 2 PAINTED UPRIGHT SPRINKLERS SHALL BE CHANGED OUT

5) WEST WAREHOUSE, INSULATION THAT HAS FALLEN AND BLOCKING SPRINKLERS SHALL BE RELOCATED

6) THE STORAGE THAT IS ON TOP OF THE METAL CAGE AT THE ENTRY TO THE WEST WAREHOUSE IS BLOCKING SPRINKLER COVERAGE AND SHALL BE REMOVED

7) AT THE NORTH CANOPY A SPRINKLER EXCEEDS THE ALLOWABLE DISTANCE OFF WALLS. MAX ALLOWABLE DISTANCE IS 7' 6"

8) SOUTH WEST CORNER OF WAREHOUSE, SPRINKLER PROTECTION SHALL BE ADDED TO THE UNDERSIDE OF THE
8' X 12' MEZZANINE OR IT SHALL BE REMOVED

9) EAST WAREHOUSE, SPRINKLERS EXCEED THE ALLOWABLE DISTANCE OFF THE WEST WALL

10) GUAGES AT THE SPRINKLER RISER SHALL BE RECALIBRATED OR CHANGED OUT

11) ON THE KENNEDY OS& Y VALVE THE PACKING HAS BEEN LEAKING AND HAS CAUSED CORROSION. THIS SHALL BE REPAIRED