Case: T09FR00259

Parcel: 12106001B


Addresses:

5851 E SPEEDWAY BL


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T09FR00259

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/06/2009 INSP - FULL Correction Required ALL REMAINING SPRINKLER DEFICIENCIES SHALL BE UNDER CONTRACT TO BE REPAIRED WITHIN 30 DAYS AND ALL OUTSTANDING BUILDING DEFICIENCIES TO BE COMPLETED WITH IN 60 DAYS
02/05/2009 INSP - FULL Correction Required THE FOLLOWING ITEMS ARE AN ADDENDUM TO THE ORIGINAL REPORT DATED 1-20-09, AND SHALL BE INCLUDED FOR COMPLIANCE

10) ALL EXTENTION CORDS SHALL BE REMOVED AND SHALL NOT BE USED IN PLACE OF PERMANRNT WIRING

11) THE COMPRESSED GAS CYLINDER SHALL BE SECURED FROM BEING KNOCKED OVER

12) iCE MACHINE ROOM - THE EGG CRATE OPEN GRATING MAY REMAIN, THE SOLID CEILING TILE AND PLYWOOD SHALL BE REMOVED.

13) THE FIRE EXTINGUISHER SHALL BE SERVICED ON AN ANNUAL BASIS AND SHALL BE HUNG FOR VISABILITY AND ACCESSABILITY.
01/20/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS

1) WALK IN COOLER HAS A SPRINKLER, STAR-ME1, WHICH WAS ON THE RECALL, AND SHALL BE CHANGED OUT

2) IN THE WORKING KITCHEN A CENTRAL MODEL G. B. SPRINKLER ON THE RECALL LIST SHALL BE CHANGED OUT

3) IN THE MENS ROOM A PENDANT HEAD HAS PAINT ON IT AND SHALL BE CHANGED OUT

4) BEHIND THE STAGE A SPRINKLER HEAD IS COVERED WITH A FOREIGN SUBSTANCE

5) NITE CLUB HIGH CEILING AREA MANY SPRINKLER HEADS ARE LOADED. ( COVERED WITH DUST )

6) AT THE REAR BEHIND THE STAGE THERE IS A BRANCH LINE WITH SPRINKLERS CLOSER THAN 4 " FROM A WALL. SPRINKLERS SHALL BE RELOCATED

7) IN THE EAST BAR AREA THERE ARE SPRINKLERS IN THE HIGH CEILING THAT ARE COVERED WITH TAPE. THE TAPE SHALL BE REMOVED

8) CLOTH DECORATIONS THAT ARE BLOCKING THE SPRAY PATTERN OF SPRINKLERS SHALL BE REMOVED

9) ALL ITEMS THAT ARE HANGING FROM SPRINKLER PIPING SHALL BE REMOVED