Case: T09FR00237

Parcel: 11619230A


Addresses:

481 W PASEO REDONDO


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00237

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/22/2009 INSP - FULL Approved REPAIR INVOICE TO SYSTEMS
04/10/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 1-15-09, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 481 W. PASEO REDONDO. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
01/15/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION OF 12-2-2008, THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE ORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE

1) TAMPER # 2 SHUT OFF @ THE BACK FLOW DID NOT ANNUNCIATE AT THE ALARM PANEL

2) THE TAMPER SWITCH AT THE P. I. V. DOES NOT WORK