Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T09FR00177
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/29/2009 | INSP - FULL | Approved | FIELD INSP. APPROVED | |
03/03/2009 | INSP - FULL | Correction Required | DURING THE LAST ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. 1) THE FOLLOWING AREAS HAVE ESCUTCHEONS MISSING ON RECESSED SPRINKLERS AND SHALL BE REPLACED, A) BY GRIDDLES IN KITCHEN B) WEST SIDE DINING AREA C) BY SOUTH EXIT PLAY AREA THESE ARE NECESSARY FOR THE COLLECTION OF HEAT, FOR THE ACTIVATION OF THE SPRINKLER HEAD. FORWARD A COPY OF THE REPAIR MANIFEST TO THIS OFFICE. |
|
02/03/2009 | INSP - FULL | Correction Required | SIR/MADAM, WHAT WAS REQUESTED WAS THE COPY OF THE ANNUAL SPRINKLER INSPECTION FOR THE BUILDING. WHAT WAS SENT WAS THE SEMI-ANNUAL REPORT FOR THE KITCHEN HOOD SYSTEM. PLEASE FORWARD THE CORRECT REPORT. THANK YOU. |
|
01/13/2009 | INSP - FULL | Correction Required | FIRE PROTECTION SYSTEMS, "SPRINKLERS", ARE REQUIRED TO BE INSPECTED AND TESTED ON AN ANNUAL BASIS. THE LAST REPORT OF INSPECTION THAT THE FIRE PREVENTION OFFICE HAS RECEIVED IS DATED 2007. PLEASE REMIT WITHIN 30 DAYS A REPORT DATED WITH IN THE LAST CALENDAR YEAR. |