Case: T09FR00177

Parcel: 12510006C


Addresses:

3605 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00177

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2009 INSP - FULL Approved FIELD INSP. APPROVED
03/03/2009 INSP - FULL Correction Required DURING THE LAST ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS.

1) THE FOLLOWING AREAS HAVE ESCUTCHEONS MISSING ON RECESSED SPRINKLERS AND SHALL BE REPLACED,
A) BY GRIDDLES IN KITCHEN
B) WEST SIDE DINING AREA
C) BY SOUTH EXIT PLAY AREA

THESE ARE NECESSARY FOR THE COLLECTION OF HEAT, FOR THE ACTIVATION OF THE SPRINKLER HEAD. FORWARD A COPY OF THE REPAIR MANIFEST TO THIS OFFICE.
02/03/2009 INSP - FULL Correction Required SIR/MADAM,
WHAT WAS REQUESTED WAS THE COPY OF THE ANNUAL SPRINKLER INSPECTION FOR THE BUILDING. WHAT WAS SENT WAS THE SEMI-ANNUAL REPORT FOR THE KITCHEN HOOD SYSTEM. PLEASE FORWARD THE CORRECT REPORT. THANK YOU.
01/13/2009 INSP - FULL Correction Required FIRE PROTECTION SYSTEMS, "SPRINKLERS", ARE REQUIRED TO BE INSPECTED AND TESTED ON AN ANNUAL BASIS. THE LAST REPORT OF INSPECTION THAT THE FIRE PREVENTION OFFICE HAS RECEIVED IS DATED 2007. PLEASE REMIT WITHIN 30 DAYS A REPORT DATED WITH IN THE LAST CALENDAR YEAR.