Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 01/13/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Sprinkler system due for annual inspection. Provide documentation. ____Fire alarm needs annual service/inspection. Provide documentation. ____Smoke detector required in every bedroom and room used for sleeping purposes. Test every smoke detector and complete smoke detector log included with this report. Signature required. Provide documentation/log upon re-inspection. ____Replace all missing smoke detectors. |
|
| 01/13/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. ____Kitchen hood extinguishing system due for service/inspection. |
|
| 01/13/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.7 Separation. All deep fat fryers shall be installed with at least a 16 inch space between the fryer and surface flames of adjacent cooking appliances. EXCEPTION: Where a steel or tempered glass baffle plate is installed at a minimum 8 inches in height between the fryer and surface flames of the adjacent cooking appliance, the requirement for a 16 inch space shall not apply. Where the fryer and the surface flames of the adjacent cooking appliance are at different horizontal planes, the minimum height or 8 inches shall be measured from the higher of the two. ____Separation or steel baffle plate required. |
|
| 01/13/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 903.3.1.1 NFPA 13 sprinkler systems. Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13... ____Sprinkler head required inside walk-in refrigerator/freezer. |