Case: T09FR00162

Parcel: 12317201C


Addresses:

1449 N CHERRY AV

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
03/23/2009 VIOL - FIRE PROTECTION SYSTEMS Approved
01/12/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.4 Extinguishing system service. Automatic
fire-extinguishing systems shall be serviced at least
every 6 months and after activation of the system.
Inspection shall be by qualified individuals, and a certificate
of inspection shall be forwarded to the fire code official
upon completion.

____Kitchen hood extinguishing system due for service/inspection.
01/12/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

____Sprinkler system needs annual inspection. Provide documentation.
____Fire Alarm needs annual service/inspection. Provide documentation.
____Repair/Replace missing fire alarm pull station in west hall.
____Smoke detectors required in every bedroom and room used for sleeping purposes. Test every smoke detector and complete smoke dectector log included with this report. Signature required. Provide documentation upon re-inspection.
01/12/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.7 Separation. All deep fat fryers shall be installed with at
least a 16 inch space between the fryer and surface flames of
adjacent cooking appliances.
EXCEPTION: Where a steel or tempered glass baffle plate is
installed at a minimum 8 inches in height between the fryer and
surface flames of the adjacent cooking appliance, the requirement
for a 16 inch space shall not apply. Where the fryer and the surface
flames of the adjacent cooking appliance are at different horizontal
planes, the minimum height or 8 inches shall be measured from the
higher of the two.

____Separation or steel baffle plate required.