Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2009 | INSP - FULL | Approved | PRE-CITATION DELETED, CORRECTION REPORT TO SYSTEMS | |
| 04/10/2009 | INSP - FULL | Correction Required | PRECCITATION SENT 4-9-09 | |
| 03/16/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 1-12-2009, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 5548 E. GRANT. IF COMPLETED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
| 01/12/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE. 1) THE WATER MOTOR GONG DID NOT WORK DURING THE MAIN DRAIN TEST, THE CHECK VALVE IS LEAKING WATER BACK INTO SYSTEM SUPPLY. 2) GUAGES AT THE SPRINKLER RISER ARE DUE FOR RECALIBRATION OR REPLACEMENT 3) FLANGE AT THE ALARM CHECK VALVE IS CORRODED DUE TO LEAKAGE |