Case: T09FR00100

Parcel: 121050220


Addresses:

5548 E GRANT RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/21/2009 INSP - FULL Approved PRE-CITATION DELETED, CORRECTION REPORT TO SYSTEMS
04/10/2009 INSP - FULL Correction Required PRECCITATION SENT 4-9-09
03/16/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 1-12-2009, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 5548 E. GRANT. IF COMPLETED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
01/12/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THE FIRE PREVENTION OFFICE.

1) THE WATER MOTOR GONG DID NOT WORK DURING THE MAIN DRAIN TEST, THE CHECK VALVE IS LEAKING WATER BACK INTO SYSTEM SUPPLY.

2) GUAGES AT THE SPRINKLER RISER ARE DUE FOR RECALIBRATION OR REPLACEMENT

3) FLANGE AT THE ALARM CHECK VALVE IS CORRODED DUE TO LEAKAGE