Case: T09FR00096

Parcel: 99999999P


Addresses:

301 N WILMOT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR00096

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2009 INSP - FULL Approved CORRECTED ADDRESS IS 310 N. WILMOT
04/08/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 1-9-2009, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 301 N. WILMOT. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
01/09/2009 INSP - FULL Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR ORDER SHALL BE FORWARDED TO THIS OFFICE.

1) THE GUAGES ON THE SPRINKLER RISER SHALL BE RECALIBRATED OR REPLACED

2) AN ADDITIONAL UPRIGHT SPRINKLER HEAD SHALL BE PLACED IN THE SPARE HEAD BOX.