Case: T09FR00074

Parcel: 13322500G


Addresses:

7151 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
01/15/2009 VIOL - MEANS OF EGRESS Approved
01/08/2009 VIOL - MEANS OF EGRESS Violation Bar on back door:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_______Remove bar and all associated hardware from door.
01/08/2009 VIOL - MEANS OF EGRESS Violation Bolt locks on back door:
TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.

______Remove bolt lock.
01/08/2009 VIOL - MEANS OF EGRESS Violation Keyed main entry:
TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background.

______ Place above-mentioned sign on or near front door in an approved manner.
01/08/2009 VIOL - MEANS OF EGRESS Violation Exit signs not lit:
TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.
_____Fix light in exit signs.