Case: T09FR00074

Parcel: 13322500G


Addresses:

7151 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
01/15/2009 VIOL - BUILDING SVCS & SYSTEMS Approved Good job!
01/08/2009 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:
TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____Replace with approved fused power strip.
01/08/2009 VIOL - BUILDING SVCS & SYSTEMS Approved Electric crossing walkway:
TFC2006 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
_______ Remove temporary wiring from crossing walkway.