Inspection Status: Approved
Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/15/2009 | VIOL - PRECAUTION AGAINST FIRE | Approved | ||
| 01/08/2009 | VIOL - PRECAUTION AGAINST FIRE | Violation | Clearance below sprinklers: TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ______Remove storage to 18 inches or more below sprinkler head. |
|
| 01/08/2009 | VIOL - PRECAUTION AGAINST FIRE | Violation | Sprinkler system: 903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901. _______ System to be tested, and tagged annually. Re-inspection date scheduled on or after January 20th, 2009. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain Re-inspection approved: ____1/14/2009_______ |